Greenheck Fan Humidifier HRE 20 User Manual

PART #461248  
READ AND SAVE THESE INSTRUCTIONS  
HEAT RECOVERY UNIT  
WITH EVAPORATIVE COOLING  
®
Models:  
HRE-20, 45, 55, & 90  
INSTALLATION, OPERATION AND MAINTENANCE MANUAL  
**WARNING**  
DISCONNECT AND SECURE TO THE "OFF" POSITION ALL ELECTRICAL POWER TO THE UNITS  
PRIOR TO INSPECTION OR SERVICING. FAILURE TO COMPLY WITH THIS SAFETY PRECAUTION  
COULD RESULT IN SERIOUS INJURY OR DEATH.  
**IMPORTANT**  
ALL FACTORY PROVIDED LIFTING LUGS MUST BE USED WHEN LIFTING THE UNITS. FAILURE TO  
COMPLY WITH THIS SAFETY PRECAUTION COULD RESULT IN PROPERTY DAMAGE, SERIOUS  
INJURY OR DEATH.  
Indirect Evaporative Cooler  
(Exhaust/Scavenger Airstream)  
Direct Evaporative Cooler  
(Outdoor/Supply Airstream)  
 
INSTALLATION  
The system design and installation should follow  
accepted industry practice, such as described in the  
ASHRAE Handbook.  
Adequate space should be left around the unit for  
piping coils and drains, filter replacement, and  
maintenance. Sufficient space should be provided on  
the side of the unit for routine service and component  
removal should that become necessary.  
Lift using lifting  
lugs and  
See pages 6 and 7 for more detail on appropriate  
clearances.  
spreader bar  
LIFTING  
Units must be lifted as it ships from the factory. All  
units are equipped with lifting lugs. THE USE OF ALL  
LIFTING LUGS IS MANDATORY WHEN LIFTING.  
Lifting should only be done with all access doors  
closed to avoid damaging the unit. To prevent  
damage to the unit cabinetry, use spreader bars.  
Spreader bars must be in position to stop cables from  
rubbing the frame or panels. Before hoisting into  
position, test lift to insure stability and balance. Avoid  
twisting or uneven lifting of the unit. Never lift units by  
weatherhoods.  
FIGURE 1  
UNIT WEIGHTS (dry weights)  
Unit Size Approx. Weight (lbs)  
HRE-20  
HRE-45  
HRE-55  
HRE-90  
1500  
2300  
3000  
5000  
V
RECOMMENDED ROOF OPENING  
Model  
U
V
EXHAUST  
INLET  
HRE-20  
HRE-45  
HRE-55  
HRE-90  
46  
54  
65  
85  
37  
39  
47  
49  
U
SUPPLY  
OUTLET  
All dimensions shown are in inches.  
FIGURE 2  
3
 
ROOF CURB MOUNTING  
1. Factory Supplied Roof Curbs  
Roof curbs are Model GKD, which are shipped in a  
knockdown kit and require field assembly (by  
others). Assembly instructions are included with  
the curb.  
2. Cut Roof Opening and Locate Curb  
Layout the unit roof opening such that the supply  
discharge & exhaust inlet of the unit will line up  
with the corresponding ductwork (refer to  
Recommended Roof Openings on page 3). Be  
sure to allow for the recommended service  
clearances. Keep the supply inlet of the unit away  
from any other exhaust fans.  
3. Install Curb  
Locate curb over roof opening and fasten in place.  
Check that the diagonal dimensions are within  
1/8 inch of each other and adjust as necessary.  
Shim as required to level. Lower unit onto curb by  
following the LIFTING instructions on page 3 of  
this manual. Note,  
roof curbs fit inside  
the unit base.  
Curb Outside Dimensions  
Model  
L
W
4. Install Duct Work  
Installation of all  
HRE-20  
HRE-45  
HRE-55  
HRE-90  
93  
51  
L
100.5  
112.75  
60.63  
71.5  
W
ducts should be  
done in accordance  
with SMACNA and  
AMCA guidelines.  
125.75 90.75  
FIGURE 3  
All dimensions shown are in inches.  
DUCT WORK CONNECTIONS  
Examples of good and poor fan-to-duct connections are shown below (See FIGURE 4). Airflow out of the fan  
should be directed straight or curve the same direction as the fan wheel rotates. Poor duct installation will result  
in low airflow and other system effects.  
n
o
i
t
n
o
i
t
Length of Straight Duct  
a
t
a
t
o
o
R
R
GOOD  
POOR  
FIGURE 4  
SUPPLY WEATHERHOOD  
Supply weatherhood will be factory mounted.  
EXHAUST WEATHERHOOD  
The exhaust weatherhood is shipped separately as a kit with its own instructions.  
EXHAUST DAMPERS  
Backdraft dampers for exhaust discharge are mounted in the unit. Motorized dampers are shipped loose (inside  
HRE) and must be field installed.  
4
 
INSTALLATION (continued)  
ELECTRICAL CONNECTIONS  
The electrical supply must be compatible with that shown on the nameplate: voltage, phase, and amperage  
capacity. The electrical supply line must be properly fused and conform to local and national electrical codes.  
All internal electrical components are pre-wired at the factory. Field electrical connections only need to be made  
inside the unit to the main disconnect (See FIGURE 5, Item #1) and the 24 volt control circuit (See FIGURE 5,  
Item #7). A door interlocking safety disconnect is provided as standard feature.  
Note: Standard factory installed electric post heaters have their own disconnect separate from the unit  
disconnect. Thus, electric post heaters require a separate power connection.  
IMPORTANT:  
Use minimum 14 ga. wire for 24 volt control power.  
Control wire resistance should not exceed 0.75 ohms (approximately 285 feet total length for  
14 ga. wire; 455 feet total length for 12 ga. wire). If wire resistance exceeds 0.75 ohms, an  
industrial-style, plug-in relay should be added to the unit control center and wired in place of  
the remote switch (between terminal blocks 2 and 3 on the control strip — See FIGURE 5,  
Item #7). The relay must be rated for at least 5 amps and have a 24 Vac coil. Failure to  
comply with these guidelines may cause motor starters to “chatter” or not pull in which can  
cause contactor failures and/or motor failures.  
TYPICAL CONTROL CENTER COMPONENTS  
1. Main Disconnect  
2. Motor Starter — Exhaust/Scavenger  
Air Fan  
3. Motor Starter — Outdoor Air Fan  
4. Motor Contactor — Energy Wheel  
5. Control Power Transformer  
(24 VAC Secondary)  
6. Energy Wheel Motor Transformer  
(230 VAC Secondary)  
(for HRE-20 & HRE-45 units with  
primary voltage greater than 230 Vac)  
7. 24 VAC Terminal strip  
1
8
5
6
8. Fuses for the control circuit, wheel  
drive transformer, and blower  
motors.  
7
4
Control Center  
O
f
f
On  
3
2
Main  
Disconnect  
Intake  
Hood  
FIGURE 5  
Exhaust  
Hood  
5
 
SERVICE CLEARANCES / ACCESS PANEL LOCATIONS for Model HRE  
HRE-20, 45, 55, and 90 units require minimum clearances for access on all sides for routine maintenance. Filter  
replacement, drain pan inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and  
belt adjustment, are examples of routine maintenance that must be performed. Blower and motor assemblies,  
energy recovery wheel cassette, coil and filter sections are always provided with a service door or panel for  
proper component access. Clearances for component removal may be greater than the service clearances,  
refer to FIGURES 6 and 7 below for these dimensions.  
Clearances for service and component removal on HRE-20 and HRE-45  
36 in.  
Exhaust  
Hood  
Access Panel  
Electrical Box  
36 in.  
Indirect  
Evap  
Section  
0 in.  
Exhaust Air  
Intake  
Clearance without  
IG Heater  
52 in.  
Clearance with  
IG Heater  
Direct  
Evap  
Section  
Access Panel  
*48 in. **64 in.  
TOP VIEW  
*Clearance for energy wheel removal on HRE-20.  
**Clearance for energy wheel removal on HRE-45.  
FIGURE 6  
Clearances for service on HRE-55 and HRE-90  
42 in.  
Exhaust  
Hood  
Access Panel  
Electrical Box  
42 in.  
Indirect  
Evap  
Section  
0 in.  
Exhaust Air  
Intake  
Clearance without  
IG Heater  
52 in.  
Clearance with  
IG Heater  
Direct  
Evap  
Section  
Access Panel  
42 in.  
TOP VIEW  
FIGURE 7  
6
 
Evaporative Cooling Modules  
Indirect Evaporative Cooler  
(Exhaust/Scavenger Airstream)  
It is important to mount the heat recovery unit level to  
ensure proper operation and water drainage. Piping  
should be of adequate size to provide sufficient  
supply of water to meet the maximum demand of the  
evaporative coolers.  
Evap Module Start-Up  
1. After the energy recovery unit is set in place, run  
the overflow and drain lines to the exterior fittings  
on the evaporative cooler (drain & overflow  
connections at unit are 34-inch female pipe thread).  
The supply line can be attached at the  
downstream side of the evaporative cooler. A  
manual shut off valve should be mounted in the  
supply line near the unit for servicing purposes.  
Also, a trap should be installed in the drain line to  
prevent sewer gas from being drawn into the unit  
(see Figure 8).  
Direct Evaporative Cooler  
(Outdoor/Supply Airstream)  
2. The cooler will be prewired by the factory.  
6. After the media break-in period, the water flow  
rate over the media needs to be checked. The  
pumps should provide enough water to saturate  
the media in 1-3 minutes. If adequate flow rate is  
not achieved, consult with the factory.  
3. Check to make sure that the pump filter is around  
the pump inlet.  
4. Turn the water on and allow the pan to fill up with  
water. The float should be adjusted to provide 2  
inches of water depth in the sump.  
7. The water bleed-off rate will now need to be  
adjusted. This measurement is 3 to 6 percent of  
the media flow rate. The recommended flow rate is  
112 to 2 GPM per  
5. Saturate the media without any airflow through the  
unit. A jumper wire is required on the terminal strip  
to provide power to the evaporative cooler pump  
(see the wiring diagram for the proper location).  
This saturation process will break-in the media and  
minimize the odors associated with the media. The  
media’s break-in period should be no less than 20  
minutes. When the process is complete, remove  
the jumper wires in the control center.  
Unit Size Media Pad Top Area  
square foot of  
HRE-20  
HRE-45  
HRE-55  
HRE-90  
1.5 ft2  
2 ft2  
2.5 ft2  
3.3 ft2  
media pad top area  
(see table at right).  
After the unit has  
been installed and  
running for two  
weeks the unit should be checked for mineral  
deposits. If there are deposits, the bleed-off rate  
needs to be increased. Some areas of the country  
have water with greater amounts of dissolved  
minerals requiring a higher bleed-off rate.  
Note: Evaporative media may foam for a short  
period following the initial start-up. Leave  
the bleed-off valve fully open until the  
foaming stops.  
8. Verify that both airflow and system static pressure  
are in agreement with the specifications. If these  
conditions are met, check for water carry over  
from the discharge side of the media. If carry over  
is observed, check the distribution header for  
holes or tears and the  
Side of HRE Unit  
Drain Line  
Evaporative  
Cooling  
water standoff tube for  
blockage.  
Overflow  
Media  
Sump  
Trap  
9. After all final  
Manual  
Shutoff  
Valve  
adjustments are made,  
remove the jumper  
wires and replace all  
Drain  
Line  
Roof Curb  
access panels. The  
unit is now ready for  
operation.  
Roof Line  
Manual Shutoff Valve  
Supply Line  
FIGURE 8  
7
 
WATER CONTROL OPTIONS FOR EVAPORATIVE COOLING  
Auto Drain and Fill with Freeze Protection  
This system will automatically drain the sump tank and fill it with fresh water at the field adjustable intervals,  
typically once every 24 hours. This flushes mineral build-up and debris from the tank to promote low  
maintenance and increase media pad life. In addition, the system will protect the evaporative cooler from  
freezing by draining the sump tank and supply line when the outside temperatures fall below the set point of the  
outside air sensor. Typically, this is set at 45º to 50º F. The auto drain and fill control box should be installed in  
an area that is shaded from direct sunlight so the outside air sensor probe will detect an accurate air  
temperature.  
Plumbing (see FIGURE 9)  
1. Run water supply line to the unit and install Water Supply Solenoid Valve (A) in this line as close to the water  
source as possible.  
2. Install Drain Solenoid Valve (B) in the supply line as indicated below. From the outlet on the drain valve, run line  
to a suitable drain location.  
3. Run an unobstructed drain line from the sump overflow to the drain as shown below.  
4. Install Sump Drain Solenoid Valve (C) in the drain line from the sump as indicated below. From the outlet on  
this drain valve, run a line to a suitable drain location.  
Note: Water Supply Solenoid Valve  
(A) is not the same as the  
Drain Solenoid valves (B) and  
(C). Make sure to use the  
Side of HRE Unit  
proper valve for each location.  
Check your local code  
Sump Drain Pipe  
requirements for proper  
installation of this type of  
system. Additional drain and  
supply plumbing may be  
needed to meet your local  
code.  
Evaporative  
Cooling  
Media  
Sump Overflow Pipe  
Sump  
Caution: All solenoid valves A, B,  
and C must be installed below the  
roof to protect the supply water line  
from freezing. If these valves cannot  
be installed below the roof, an  
Roof Curb  
Roof Line  
Sump Drain  
Solenoid  
Valve (C)  
alternate method must be used to  
protect these lines from freezing.  
Water Supply  
Solenoid Valve (A)  
Drain  
Solenoid  
Valve (B)  
Supply Line  
Trap  
Drain  
Line  
8
 
TROUBLE SHOOTING FOR EVAPORATIVE MODULE  
Symptom  
Solution  
Insufficient water  
A. Check water level in base pan. The level should be at 2 inches.  
B. Check the pump filter at the inlet. Clean the filter if clogged or dirty.  
C. If pump is not operating, check wiring for loose connections and proper  
voltage.  
volume or recirculation  
pump not operating  
Irregular water  
distribution on cooling  
media  
Water distribution header, orifices or media partially blocked or plugged.  
Remove evaporative cooler from unit.  
Disassemble and clean distribution header, orifices and media.  
A. Check water flow across the face of the media. Irregular water distribution  
must be corrected (see above)  
Scale and mineral  
deposit formation on  
face of media  
B. Increase water flow rate. Media is self cleaning with flow rate of 112 to 2  
gpm per square foot of media top area. Generally this flow rate prevents  
dissolved solvents from collecting on the media. To prevent further trouble,  
flush and clean the system more frequently.  
C. If this condition persists, chemicals may need to be added. Water pH  
should be maintained between 6 and 8.  
A. Irregular water distribution on face of media (see above).  
B. Average face velocity exceeds 650 fpm. Decrease fan rpm and airflow.  
C. Localized face velocities exceeding 650 fpm. Air filters or media face area  
is partially blocked. Clean or replace air filters and media.  
D. Check the overflow for blockage.  
Water Carry-Over  
A. Irregular water distribution over face of media (see above).  
B. Check for uniform air flow.  
Inadequate cooling  
C. Check outside wet-bulb temperature. High wet-bulb temperatures can  
decrease performance.  
D. Check water flow rate over media. Flow rate should be 112 to 2 gpm per  
square foot of media top area.  
A. Check the water bleed off rate and make sure that it is not excessive.  
B. Check water level in base pan. The level should be at 2 inches.  
Excessive water  
discharge into drain  
Pad installed backwards. To get the  
performance from the cooling pads,  
they must be installed properly. The  
pads are manufactured with 15/45  
degree flute angles. The pads must  
always be installed with the steeper  
flute angle sloping down toward the  
entering air side. See figure on right.  
Poor performance after  
cooling pad  
replacement  
45°  
Entering Air  
Leaving Air  
15°  
9
 
EVAPORATIVE COOLING MAINTENANCE  
Regularly scheduled maintenance is the key to peak  
performance, minimized cost, and extended life of the  
evaporative cooler. The following is a checklist of  
Continuous operation in this manner may cause  
serious damage and void the warranty.  
items that need to be looked at on a regular basis.  
7. At the end of each cooling season the  
evaporative cooler should be thoroughly cleaned.  
A dispersant and biocide (consult water  
1. The media should be checked for mineral and  
foreign material deposits that have built up. If  
these items are left on the media, the life and  
performance of the unit will be greatly reduced.  
Also, there are risks of water carry over when this  
type of condition exists. When signs of mineral  
build-up are noticed, you should increase the  
bleed off rate. If this does not solve the problem,  
chemicals may need to be added to the water.  
The evaporative pads tend to be self cleaning.  
Depending on water quality and system  
treatment consultant for suitable materials and  
dosage levels) should be recirculated for 12 to 24  
hours prior to performing the following steps:  
a) Disconnect power to unit.  
b) Shut off all water to the unit  
c) Open evaporative cooling section door  
d) Flush distribution headers and media for 20  
minutes  
e) Turn off pumps and drain all water distribution  
piping, headers, etc.  
maintenance, the useful life of the pads should  
be 3 to 5 years.  
f) Dry media completely by running blowers.  
g) Brush media as described in Paragraph 2 and  
perform steps d and e again.  
h) Clean all remaining components (i.e. sump,  
pump, etc.) of any mineral deposits or foreign  
materials  
2. The media should be periodically brushed lightly  
with a soft bristle brush in an up and down  
motion (never brush side-to-side) while flushing  
with water. This will also aid in reducing the  
amount of foreign material build-up.  
i) Replace all worn or non-functioning parts  
j) Reassemble the cooling unit.  
k) Close cooling section door.  
3. The water should be shut off and all the lines  
drained when the temperature drops below 50°F.  
l) Turn the main disconnect 'ON', leaving the  
cooling switch in the 'OFF' position.  
4. When the evaporative cooler is going to be used  
for the first time each season, it is recommended  
that the media be flushed with clean water for a  
period of 2 minutes (see Evap Module Start-Up  
on page 7).  
8. If the evaporative cooler will be turned off during  
the cooling season for an extended period of  
time, it is recommended that the media be dried  
out. This can be accomplished by allowing the  
blowers to continue to run for 1-2 hours. Doing  
so, will prevent organic build-up on the media  
and subsequent odors getting into the space.  
5. At the beginning of each cooling season, the  
upright recirculating pump should have the shaft  
oiled and spun to eliminate the potential of  
seizing and pump burn out.  
9. Media should be permitted to dry once per week  
by allowing the blowers to run for 1-2 hours.  
6. If the cooling media was removed from the unit,  
check to make sure that is not installed  
backwards. If the media is installed backwards,  
there will be large amounts of water carry over  
downstream of the evaporative cooler.  
10. A flush cycle should be performed weekly for one  
hour with the fans off.  
10  
 
WATER COIL APPLICATION  
RECOMMENDATIONS  
Factory installed heating components are  
mounted down stream of the energy wheel (and  
direct evaporative cooler if supplied) on the  
supply air side of the unit.  
See FIGURE 10 for coil connection location. Coil  
connections are located external to the unit as  
shown. Coil connections that are not external  
have been ordered from the factory with interior  
or exhaust air stream coil connections.  
Water coil  
connections  
FIGURE 10  
1. Piping should be in accordance with accepted  
industry standards. Pipework should be supported  
independently of the coils. Water connections are  
male NPT iron pipe. When installing couplings, do  
not apply undue stress to the connection  
extending through the unit. Use a backup pipe  
wrench to avoid breaking the weld between coil  
connection and header.  
release all of the air from the coil. To maintain heat  
transfer capacity, periodically vent any air in coil.  
4. Water coils are not normally recommended for use  
with entering air temperatures below 40oF;  
however, the energy recovery wheel maintains a  
pre-coil temperature higher than 40oF. No control  
system can be depended on to be 100% safe  
against freeze-up with water coils. Glycol  
solutions or brines are the only safe media for  
operation of water coils with low entering air  
conditions.  
2. Connect the WATER SUPPLY TO THE BOTTOM  
CONNECTION on the air leaving side and the  
WATER RETURN TO THE TOP CONNECTION on  
the air entering side. To insure proper venting, an  
external air vent in the piping is recommended.  
Connecting the supply and/or return in any other  
manner will result in very poor performance. Be  
sure to replace factory installed grommets around  
coil connections if removed for piping. Failure to  
replace grommets will result in water leakage into  
the unit and altered performance.  
CONTINUOUS WATER CIRCULATION THROUGH  
THE COIL AT ALL TIMES IS HIGHLY  
RECOMMENDED.  
5. Pipe sizes for the system must be selected on the  
basis of the head (pressure) available from the  
circulation pump. The velocity should not exceed  
6 feet per second and the friction loss should be  
approximately 3 feet of water column per 100 feet  
of pipe.  
3. The air vent at the uppermost point should be  
temporarily opened during system start-up to  
11